The valve sits at 50%. The 475 is on the loop. The board wants the unit back in twenty minutes.
Auto Travel Calibration takes four. The rest of the window decides whether the valve holds position when the process returns.
What calibration is not
Calibration is not tuning. Tuning sets how the valve answers an error. Calibration sets what 0% and 100% mean. A valve with fresh calibration and a bad tune hunts. A valve with a good tune and a stale calibration drifts.
Calibration is not a repair. A worn relay passes ATC at bench pressure and fails on the first process step.
Four checks before the loop goes to manual
Supply pressure. Read the gauge at the filter regulator, not at the header. The DVC6200 accepts supply to 150 psig; confirm the ceiling on the nameplate before you raise it. Set the regulator above the actuator requirement at the spring end, with margin for line loss. A controller starved of air passes calibration and stalls near 70% on the first move.
Tubing. Half-inch line from positioner or booster to actuator. A kink or a finger-tight fitting shows as a slow stroke and no alarm.
Feedback. The DVC6200 uses magnetic, linkage-less feedback. Inspect the magnet and arm before power-up. A bent bracket shows as a travel sensor alert during the run.
Safe state. Bypass the valve or block the process. Send a full stroke by hand and watch for a mechanical stop in the path.
Signal check
Drive the loop at 4, 12 and 20 mA from the controller or a calibrator. Read travel on the local display. Three points catch wiring and scaling faults that ATC will hide.
The menu path
- Local interface: Setup > Calibration > Auto Travel Calibration
- ValveLink: Device > Calibrate > Auto Travel Calibration
- 475: Device Setup > Calibration > Auto Travel Calibration
The label is Auto Travel Calibration. A procedure that sends you to "Auto Stroke" sends you to a screen that does not exist.
What ATC does
The controller drives the valve to both ends, records the stops, sets 0% and 100%, compares feedback against command, and stores the values it found. Transient alerts appear during the run. Note them, clear them, then read the result.
Pass criteria
Command 0, 25, 50, 75 and 100%. At each point:
Travel deviation inside the device alert threshold, with no active alert.
Five minutes at 50% with no drift.
Stroke time inside the actuator specification, both directions.
Write the numbers down. "Looks smooth" is not a result. A calibration report with no numbers is a signature on trust.
When it fails
| Symptom | Check first | Likely cause |
|---|---|---|
| No movement, no air | gauge at regulator | blocked filter, dead regulator |
| No movement, air at relay | drive signal at I/P | I/P or relay |
| Movement, no feedback | magnet and arm | feedback module |
| Fails at one end | travel stop, bracket | mechanical limit |
| Hunts after ATC | tubing, gain | tuning, oversized actuator |
Two rules. A valve that fails at the same travel every run has a mechanical fault, not a calibration fault. A valve that passes ATC and drifts under load has a supply fault.
Manual calibration: three cases
Split range. Custom characterization. An actuator with a stop ATC cannot reach.
Outside those cases, manual calibration covers a fault. Find the fault.
Split range: two valves, one signal
A split-ranged pair shares a 4-20 mA loop. Valve A takes 4-12 mA; valve B takes 12-20 mA. Set the input range on each controller to its half, then calibrate travel across that half. Test with the other valve isolated: drive 4, 8 and 12 mA and confirm A reaches 0, 50 and 100%. A pair calibrated on a full 4-20 mA range fights at the crossover, and the trend shows a dead band in the middle of the loop.
Custom characterization: 21 points
The DVC6200 stores a custom characteristic as a table of setpoint against travel target, 21 points. Path: Configure > Detailed Setup > Response Control > Input Characterization. Use it when the trim is not linear, or when two valves in a split range need matched gain at the crossover. Enter the table, then stroke the valve at five points and compare travel against the table.
A custom curve hides a mechanical fault. If travel lags at 30% on a linear curve, it will lag on a custom curve. Fix the valve first.
DVC6200, DVC6200HC, DVC6200 SIS
Emerson's catalogue lists DVC6200, DVC6200f, DVC6200p and DVC6200 SIS. "DVC6200HC" comes from resale listings; read it as a description of the build (double-acting, high-capacity relay), not a model. Ask for the full model string and the relay part number before you order a spare.
The SIS version adds partial stroke testing, SIS diagnostics, and the certification a safety loop needs. The proof-test record belongs in the safety file, not the maintenance file.
What ATC cannot see
ATC measures travel. It does not measure force. Sticking packing, a bent stem, or a valve body full of scale passes at bench conditions and shows under load. If the valve passes and the loop swings, the problem sits downstream of the positioner.
Reading a PST curve
A partial stroke test steps the valve off its seat by a set percentage, holds, then returns. ValveLink plots command, travel and supply pressure against time. Read four things: dead time before travel starts, the slope of the first move, steps in the line, and the return.
A slower first move with a clean slope points at packing or stem friction. A pressure dip at the start points at supply or tubing. A travel line that steps points at stick-slip. A return that overshoots points at relay or tuning.
Compare against the baseline for that valve. A PST does not replace the full stroke proof test.
What to record
Supply pressure at the start. Ambient temperature. Stroke time, open and close. Deviation at five points. Alerts cleared. Firmware version. Photo of the tag.
Save the ValveLink report to the asset file. A laptop is not an archive.
Parts that fail this test
Relay seats wear. I/P assemblies fail. Feedback modules drift after a stem repair. Keep one relay and one feedback module per ten valves, and a filter element per regulator.