One of our customers sent us a photo of a fault code on their screen. "The valve just stopped working. Can you tell me what this code means?"
We get questions like this all the time in customer support. Maintenance engineers don't have time to flip through manuals. They need a quick answer: What does this code mean? Where do I start? Can I fix it now?
Fisher DVC6200 positioners have built-in diagnostics. Fault codes are the first clue, but not every code says "replace this part." Sometimes it says "check here first."
I put this guide together with the most common DVC6200 fault codes and troubleshooting steps for each one. Next time you see a code, you can look it up here instead of grabbing the manual.
Here's a quick reference table to get you started.
Fault Code Quick Reference Table
|
Code |
Meaning |
Most Likely Cause |
Recommended Action |
|
IO_1 |
I/P Converter Fault |
I/P module failure or clogged nozzle |
Clean nozzle first; replace I/P module if needed |
|
IO_2 |
I/P Converter Deviation |
Unstable air supply or aging module |
Check air supply, run calibration |
|
FLT_1 |
Calibration Failed |
Feedback module or valve binding |
Manual stroke check, re-calibrate |
|
FLT_2 |
Feedback Signal Lost |
Feedback module or loose arm |
Check feedback arm and mounting |
|
COM_1 |
HART Communication Error |
Loop resistance or wiring issue |
Check wiring and loop resistance |
|
COM_2 |
HART Communication Intermittent |
Module failure or bus conflict |
Check bus load, verify module status |
|
PWR_1 |
Supply Voltage Low |
Low loop voltage |
Check power supply |
|
PWR_2 |
Supply Voltage High |
Voltage above rated range |
Check power module output |
|
DSP_1 |
Display Module Fault |
Loose cable or display failure |
Check cable; replace display if needed |
|
AIR_1 |
Low Supply Air Pressure |
Low air supply or leak |
Check air supply and tubing |
Note: Fault code numbers may vary slightly across different DVC6200 firmware versions. Always verify against your device and refer to the fault code list in the product manual.
Fault Diagnosis Flowchart
Once you have the fault code, follow this decision tree. You don't need to guess which fault type it is-the code tells you.

How to use this flowchart:
When the positioner alarms, check the first letter(s) of the fault code (COM / FLT / IO / DSP / PWR / AIR)
Start with power and air checks-this is the fastest baseline check and catches 80% of issues early
Follow the branch for your code type-the code itself tells you where to go
Stop when you reach "Done"-the issue is resolved
If you reach "Replace/Check module"-all other causes have been ruled out
Quick Decision Path (for fast reference)
|
Code Prefix |
Primary Check |
Secondary Check |
Final Action |
|
COM_ |
Wiring + loop resistance |
Bus load + HART version |
Replace comm. module |
|
FLT_ |
Feedback arm + mounting |
Manual stroke test |
Replace feedback module |
|
IO_ |
Signal + air supply |
Clean nozzle/flapper |
Replace I/P module |
|
DSP_ |
Cable connection |
- |
Replace display module |
|
PWR_ |
Supply voltage |
Power module output |
Replace power module |
|
AIR_ |
Supply air pressure |
Leak check + filter |
Service pneumatic module |
Detailed troubleshooting steps are below.
IO_1: I/P Converter Fault
What you'll see: Input signal is present but no pneumatic output. Valve doesn't move.
What to check: I/P module failure, clogged nozzle, dirty air supply.
What to do:
Confirm you have a 4-20mA input signal with a multimeter.
Check that supply air pressure is within the rated range (1.4–7 bar).
If signal is fine but no output, remove the I/P module and check the nozzle-try blowing it clean with compressed air.
Still not working? Replace the I/P module.
Run an auto-calibration after replacement.
Spare parts tip: The I/P converter is one of the most common failure points-keep one in stock.
IO_2: I/P Converter Deviation
What you'll see: Output pressure is unstable. The valve position hunts or oscillates.
What to check: Unstable air supply, aging I/P module, signal noise.
What to do:
Monitor supply air pressure with a gauge-check for fluctuations.
Confirm the air supply is dry, oil-free, and clean.
Re-run the auto-calibration.
Still unstable after calibration? The I/P module may be aging-consider replacing it.
FLT_1: Calibration Failed
What you'll see: Auto-calibration errors out mid-process. Cannot complete.
What to check: Feedback module issue, incorrect feedback arm angle, valve binding, actuator problem.
What to do:
Send open/close commands from a communicator and watch how the valve responds.
If movement is rough, check the valve and actuator for mechanical binding-try a manual pump.
Verify the feedback arm angle is within spec (see product manual, Section 3).
Loosen the feedback arm, confirm free movement, then re-tighten.
Re-run the calibration procedure. Still failing? The feedback module may be damaged.
FLT_2: Feedback Signal Lost
What you'll see: Valve position reading on the display doesn't match actual position. Positioner keeps oscillating.
What to check: Feedback module failure, loose feedback arm, loose mounting bracket.
What to do:
Look at the actual valve stem position and compare with the display reading.
They match? The reading is fine-the issue is likely in the control signal.
They don't match? Check if the feedback arm is loose or disconnected.
Check that the feedback module mounting bracket is secure.
Feedback arm is fine but the reading is still wrong? The feedback module may be damaged.
COM_1: HART Communication Error
What you'll see: Handheld communicator can't connect. DCS stops receiving feedback.
What to check: Low loop resistance (HART needs ≥250Ω), loose/incorrect wiring, low supply voltage, communication module failure.
What to do:
Check wiring-look for loose connections, reverse polarity, oxidation.
Measure loop resistance with a multimeter. Below 250Ω? Add a resistor in the loop.
Check supply voltage against the DVC6200's rated range.
Check if other devices on the same bus are causing address conflicts or bus overload.
Verify the communicator model supports the current HART version (DVC6200 supports HART 5/7).
If all checks pass but still no connection, try a HART reset command or cycle power.
Still not working? The communication module may need servicing.
Important: Fisher communication modules are not interchangeable across protocols-HART, Foundation Fieldbus, and Profibus each use different hardware. If the module is damaged, check the label on your original before you order a replacement.
COM_2: HART Communication Intermittent
What you'll see: Communication connects occasionally but drops out frequently. Unstable signal quality.
What to check: Intermittent contact, voltage fluctuations, excessive bus load, failing communication module.
What to do:
Check terminals for oxidation or loose connections.
Measure supply voltage for stability-watch for fluctuations.
Check the number of devices on the loop (HART recommends no more than 15 devices).
Use a HART communicator to read the device status-look for other concurrent errors.
Communication is still unstable? The module may be failing.
PWR_1: Supply Voltage Low
What you'll see: Positioner won't start up, or powers off during operation. Screen flickers.
What to check: Low supply voltage, poor terminal contact, insufficient loop voltage.
What to do:
Measure terminal voltage with a multimeter-confirm it's within the DVC6200 rated range (typically 12-42VDC; check product manual Section 2).
Check terminals for oxidation or looseness.
Voltage low? Check the power supply and the loop for shorts or opens.
Voltage is fine but the positioner still won't start? There may be an internal power circuit issue.
PWR_2: Supply Voltage High
What you'll see: Positioner runs abnormally, temperature rises noticeably, or it resets intermittently.
What to check: Power module output issue, voltage above rated range.
What to do:
Measure terminal voltage-is it above the DVC6200's rated maximum?
Check if the power module output is stable.
Voltage too high? Replace or adjust the power module.
Voltage is within range but the code persists-cycle power and check if the code clears.
DSP_1: Display Module Fault
What you'll see: Screen blank, garbled, or abnormally dim-but the positioner still works (valve moves, communication fine).
What to check: Loose display cable, display module failure, temperature extremes.
What to do:
Confirm the positioner itself is still working-valve movement and signal feedback mean the main board is alive.
Power down, open the housing, and check the display cable connection to the main board.
Re-seat the cable and power back up.
Cable is fine but the screen still fails? Replace the display module.
No calibration needed after display module replacement.
AIR_1: Low Supply Air Pressure
What you'll see: Valve moves slowly or lacks force. Can't reach full open/close. You can hear air hissing.
What to check: Low supply air, air leak, worn seals in the pneumatic module, clogged filter.
What to do:
Check the pressure gauge-is it within the rated range (1.4–7 bar)?
Listen for air leaks-use leak detection fluid to pinpoint leaks.
Check if the filter is clogged or the air supply contains water/oil.
Pressure is fine but still low force? The pneumatic module may have worn seals.
About Fault Code Reset
Power the positioner back up after a repair, and most fault codes will clear themselves. But if you manually clear a code without actually fixing the problem, it'll just come back when the positioner runs its next diagnostic check. So always make sure the issue is actually fixed before you clear any codes.
Bottom Line
Fisher DVC6200 fault codes are there to help you narrow things down-not to scare you. Think of them as the starting point, not the verdict.
This guide has the most common codes and what to do about them. Next time your positioner alarms, run through the checks here first-you'll usually find the problem faster than if you just start tearing things apart.
If you've confirmed which module has failed and need replacement parts or technical support, contact us for module availability and pricing.





